HZJD-2Z - TRANSFORMER OIL TAN DELTA
TESTER
IEC-ASTM COMPLIANT DIELECTRIC LOSS AND
RESISTIVITY MEASUREMENT DEVICE FOR TRANSFORMER OIL
In high-voltage power systems, the
quality of insulating oil directly affects the safety and lifespan of
transformers.
The HZJD-2Z Transformer Oil Tan Delta
Tester is a specialized device used to measure:
• Dielectric loss coefficient (Tan
Delta)
• Relative Permittivity
• DC resistivity of insulating oil
The device is designed according to
GB/T5654-2007 standards, conforming to IEC 60247 and ASTM D924, meeting the
testing requirements in power plants, substations, and testing centers.
PRACTICAL APPLICATIONS
• Transformer oil quality testing
• Insulation oil aging assessment
• Oil quality control before
commissioning
• Electrical and energy industry
laboratories
• High-voltage power system maintenance
and repair units
HIGHLIGHTS OF HZJD-2Z
1. Integrated Structure – Fully
Automatic Operation
The device is integrated into a single
system:
• 3-electrode test chamber
• PID temperature controller
• Dielectric loss bridge
• AC test power supply
• High-voltage DC power supply
• SF6 internal reference capacitor
• High resistance meter
The entire measurement process is fully
automated – the operator only needs to follow the instructions on the LCD
screen.
2. GB/T5654-2007 Standard 3-Electrode
Test Chamber
• Electrode spacing: 2mm
• Reduces parasitic capacitance and
leakage
• Features an automatic oil drain
system using a solenoid valve
• Allows sample rinsing without
removing the cell
Increases accuracy and saves operating
time.
3. Medium Frequency + PID Induction
Heating
• Non-contact heating
• Uniform and rapid heating
• Temperature control error: ±0.5℃
• Temperature setting range: 0 – 125℃
Includes a temperature limit relay that
automatically shuts off when exceeding 120℃ – ensuring safety.
4. High Accuracy – Long-Term Stability
• SF6 internal pressure-sensitive
capacitors – independent of ambient temperature and humidity
• AC power supply using AC-DC-AC
technology, eliminating the influence of grid voltage fluctuations
• Stable operation even when using a
generator
5. Complete Safety Protection System
Automatic shutdown in case of:
• Overvoltage
• Overcurrent
• High-voltage short circuit
• Temperature sensor failure
Warnings are displayed directly on the
screen.
MAIN TECHNICAL SPECIFICATIONS
Tan Delta
• Measurement range: 0.00001 – 100
• Accuracy: ±(1% of measured value +
0.0001)
Dielectric constant
• Measurement range: 1 – 30
• Accuracy: ±1%
Resistivity
• Measurement range: 2.5MΩ·m – 20TΩ·m
• Resolution: ±10%
Test voltage
• AC: 0 – 2000V
• DC: 0 – 500V
Power supply
• AC 220V ±22V (50/60Hz)
Dimensions – Weight
• 500 × 360 × 420 mm
• 22 kg
BENEFITS OF IMPLEMENTATION IN
ENTERPRISES
✔ Inspection Accurate transformer oil
quality control
✔ Reduces the risk of power system
failures
✔ Meets international inspection
standards
✔ Increases the reliability of
substation operation
✔ Saves inspection time
LEDANCO – POWER INDUSTRY TESTING
EQUIPMENT SOLUTIONS
Le Dan Trading and Service Co., Ltd.
(LEDANCO) provides:
• In-depth technical consulting
• Operation guidance & technology
transfer
• Maintenance and calibration support
• Supply of genuine equipment
Delivery method: Nationwide.
- Free in city. HCM
- In the station or express delivery if the customer in outside the province (customers pay shipping costs themselves)
Commitment to customers:
==> Supplying genuine goods (CO / CQ attached), 100% new (with the original belt)
==> Ensure customer's interests when buying products while in warranty, and maintenance for life.
=============== ///=============
LE DAN SERVICE TRADING CO., LTD
Address: 154/29 Pham Van Hai St., Ward Tan Son Hoa, HCM City,VN
Phone: 02839914859 - 02839914860 - Hotline: 0918121454
Email : ledanco03@gmail.com